Your cart is empty.

The Federal Signal GEN-IIC-25W is an explosion-proof, 25-watt non-metallic loudspeaker engineered for reliable public address and general alarm signaling in hazardous locations. Certified ATEX and IECEx Zone 1 (Gas Group IIC) and IP66-rated, this GRP-housed horn delivers crystal-clear audio up to 123 dBA in severe chemical, offshore, and oil & gas environments.
| Country of Origin | United States (US) |
| ATEX Rating | II 2 G Ex db IIB+H2 T4 Gb or Ex db IIC T4 Gb | II 2 D Ex tb IIIC T135°C Db |
| IECEx Certified | Ex db IIC T4 Gb (-50°C to 65°C) | Ex db IIC T5 Gb (-50°C to 53°C)| Ex tb IIIC T135°C Db |
The Federal Signal GEN-IIC-25W is an explosion-proof, 25-watt non-metallic re-entrant horn loudspeaker designed specifically for high-reliability public address and general alarm applications in hazardous industrial environments. Built with high-durability glass-reinforced polyester (GRP) and certified ATEX and IECEx Zone 1 for Gas Group IIC, it delivers vital emergency notifications and voice broadcasts without risk of ignition. Its robust construction and IP66 rating ensure superior resistance against corrosion, dust, moisture, and harsh chemical exposure in heavy industrial operations.
Delivering a maximum audio output of up to 123 dBA at 1 meter, the GEN-IIC-25W features a 100 Vrms line transformer with selectable power taps (2 W, 4 W, 6 W, 25 W) to easily adjust sound pressure levels based on surrounding noise conditions. Equipped with a ratcheted stainless steel U-mounting bracket that locks firmly into position without slipping, it allows flexible positioning and simple installation across challenging field spaces. Designed for extreme service, it operates reliably across extreme temperature ranges from -50°C to +65°C (-58°F to +149°F).
✅ ATEX and IECEx Certified for Zone 1, Gas Group IIC
✅ 100 Vrms transformer input with adjustable power taps ( 25 W)
✅ Ingress Protection IP66 and UV solar-resistant non-metallic housing
✅ Powerful re-entrant horn design producing up to 123 +/-3 dBA at 1 m
✅ Extreme operating temperature range from -50°C to +65°C (-58°F to +149°F)
✅ Corrosion-resistant, anti-static Glass Reinforced Polyester (GRP) housing
✅ Stainless steel ratcheted U-mounting bracket prevents slipping
✅ Dual M20 x 1.5 mm threaded cable entries for easy field wiring
✅ Suitable for Gas Group IIC and Combustible Dust Group IIIC environments
🔹 Standard Version (GEN-IIC-25W): Includes standard ratcheted stainless steel U-mounting bracket.
| Feature | Details |
|---|---|
| Model | GEN-IIC-25W |
| Manufacturer | Federal Signal |
| Audio Input | 100 Vrms |
| Power Handling | Max 25 W |
| Power Taps & SPL Output | 25 W (123 dBA) at 1 m |
| Housing Material | Anti-static Glass Reinforced Polyester (GRP), UV Solar Resistant |
| Color | Black |
| ATEX Certification | UL 22 ATEX 2889X (Ex II 2GD) |
| IECEx Certification | IECEx UL 22.0094X |
| Hazardous Protection Rating | Ex db IIC T4 Gb / T5 Gb, Ex tb IIIC T135°C Db |
| Ingress Protection | IP66 |
| Operating Temperature | -50°C to +65°C (-58°F to +149°F) |
| Cable Entries | 2x M20 x 1.5 mm threaded gland entries |
| Cable Terminations | 0.5 to 4 mm² (20 to 12 AWG) |
| Dimensions | 232.2 x 347 mm (9.1 x 13.7 in) |
| Net Weight | 14.5 lb (6.6 kg) |
| Shipping Weight | 16.5 lb (7.5 kg) |
🔗 ATEX Certificate UL 22 ATEX 2889X – Certified Ex II 2GD
🔗 IECEx Certificate IECEx UL 22.0094X – Certified for Zone 1 explosion-proof areas
🔗 Protection Rating: Ex db IIC T4 Gb (-50°C to +65°C) / Ex tb IIIC T135°C Db
🔗 Ingress Protection: IP66 rated for complete dust exclusion and heavy water jets
🔗 Download Datasheet
🔹 Oil & Gas Offshore Platforms & Refineries
🔹 Chemical & Petrochemical Processing Facilities
🔹 Mining & Bulk Material Handling
🔹 Marine & Port Terminals
🔹 Heavy Manufacturing & Industrial Plants
📦 1x Federal Signal GEN-IIC-25W Loudspeaker
📦 1x Stainless Steel Ratcheted U-Mounting Bracket
📦 1x Internal Terminal Block Assembly
📦 1x Installation & Documentation Kit
📦 Lead Time: 3 - 4 weeks
📍 Shipping Terms: Worldwide / Expedited Options
💳 Payment Options: Credit Card, PayPal, Net 30 Terms
Is the GEN-IIC-25W certified for hydrogen environments?
Yes, Gas Group IIC certification covers hydrogen (IIC) environments as well as IIB and IIA applications.
Can the sound output level be adjusted?
Yes, the unit features built-in transformer taps allowing power adjustments at 2 W (104 dBA), 4 W (110.5 dBA), 6 W (117 dBA), and 25 W (123 dBA).
What is the difference between the standard model and the ISMT model?
The ISMT model includes an intelligent speaker monitoring and tapping interface built-in, enabling remote status checking and tapping without requiring manual access to the speaker.
What mounting options are available?
It comes standard with a ratcheted stainless steel U-bracket, and an optional 3-hole swivel mounting bracket (K8595172A) is available for multi-angle adjustment.
No reviews yet — be the first to review this product.