Tomar GNEXS1 Alarm Horn Sounder 117dB (A)-Intrinsically Safe
Tomar Electronics flameproof Tomar GNEXS1 Alarm Horn Sounder 117dB (A)-Intrinsically Safe, sounder stands as an exemplary solution tailored for Zone 1 and Zone 2 applications, holding certifications from ATEX and IECEx. Boasting a commanding sound level of up to 117dB (A) at a distance of 1 meter, this intrinsically safe alarm system offers not only power but also flexibility. With a selection of 64 alarm tones and four remotely selectable stages, users have the freedom to customize their alert system.
Independently selectable alarm tone frequencies for the initial two stages add a layer of adaptability. Constructed with enclosures made from durable glass-reinforced polyester (GRP), available in a natural red hue or alternative colors, the GNExS1 ensures resilience against environmental factors. The re-entrant flare horn, crafted from high-impact, fire-retardant ABS, further guarantees robustness.
Facilitating installation flexibility, the device incorporates two M20 cable entries. Its large termination areas house in and out terminals, simplifying the connection process. The GNExS1 achieves an ingress protection rating of IP66/67, safeguarding against dust and water, making it suitable for challenging conditions.
Designed to accommodate diverse power systems, the AC voltage model operates within a range of 100-260V AC and DC. Specifically, it proves compatible with 110V DC gas detection systems.
Features:
- Automatic Synchronization: Effortless integration into multi-sounder systems with automatic synchronization.
- Very Large Termination Area: Ample space provided for secure and convenient terminations, ensuring ease of installation.
- Ratchet Adjustable Stainless Steel ‘U’ Bracket: Equipped with a robust and adjustable stainless steel bracket for flexible and sturdy mounting.
- IN & OUT Terminals: Conveniently designed with both input and output terminals, facilitating straightforward connections.
- Independently Selectable Tones for 1st & 2nd Stages: Customizable alarm tones for the first and second stages, allowing tailored alert configurations.
- Four Remotely Switched Stages/Channels: Enhanced flexibility with four remotely switchable stages or channels for diversified signaling options.
Approvals
- ATEX certificate: SIRA 13ATEX1139X, EN 60079-0 : 2012, EN60079-1: 2007
- ECEx certificate: IECEx SIR 13.0029X, IEC 60079-0 : 2011 (Ed6), IEC 60079-1: 2007 (Ed6)
- TR-CU Ex EAC certificate: RU C-GB.AA71.B.00109
Coding
- II 2G Ex d IIC T4 Ta. -60° to +50°C
- II 2G Ex d IIC T3 Ta. -60° to +70°C
- II 2G Ex d IIB T6 Ta. -60° to +50°C
- II 2G Ex d IIB T5 Ta. -60° to +65°C
- II 2G Ex d IIB T4 Ta. -60° to +70°C
Tomar GNEXS1 Alarm Horn Sounder 117dB (A)
Specifications:
Technical Data | ||
Item | Description | |
Maximum output | 117dB (A) @ 1 meter [108dB (A) @ 10ft/3m] | |
Nominal output | 110dB (A) @ 1m +/- 3dB - Tone 2 [101dB (A) @ 10ft/3m] | |
No. of tones | 64 (UKOOA / PFEER compliant) | |
No. of stages | 4 | |
Volume control | Max. 110dB (A); Min. 72dB (A) - Tone 44 | |
Effective range | 100m/328ft @ 1 KHz | |
Voltages DC | 24vdc (10-30vdc), 48vdc (38-60vdc) | |
Voltages AC | 230vac (100-260vac/dc) | |
Stage switching | Negative or positive | |
Ingress protection | IP66/67 | |
Enclosure material | GRP (glass reinforced polyester) | |
Color | RAL3000 Red (others available on request) | |
Flare Material | High impact UL94 V0 & 5VA FR ABS (Red) | |
Cable entries | Dual M20 ISO | |
Terminals | 0.5 - 2.5mm² (20-14 AWG) | |
Enclosure volume | <2liters | |
Line monitoring | Blocking diode included EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor or diode (DC versions) can be fitted | |
Weight | 3.00kg/6.6Ibs AC: 3.20kg/7.04Ibs | |
Ordering Information | ||
Model | Voltage | Current |
GNExS1-024 | 10-30 VDC | 140mA @ 24 VDC |
GNExS1-048 | 38-60 VDC | 73mA @ 48 VDC |
GNExS1-115-230 | 100-260 VAC/DC 50/60Hz | 86mA @115 VAC / 75mA @ 230 VAC |