Intrinsically Safe Air Conditioner Kooltronic HL48LV Series is Class 1 Division 1 and Class 1 Division 2 certified to use in hazardous areas. With NEMA 4/4x ratings. Rated at 9000 BTU/HR and operable at 115VAC and 208/230VAC/1/50/60HZ. It features closed-loop cooling, compressor short cycling protector, programmable thermostat, programmable temperature alarm, stainless steel shell, both evaporator and condenser coils are epoxy coated and designed to withstand shock and vibration.
| Country of Origin | United States (US) |
| Hazardous Area Rating | Class 1 Division 1 and Class 1 Division 2 |
Intrinsically Safe Air Conditioner Kooltronic HL48LV Series is Class 1 Division 1 and Class 1 Division 2 certified to use in hazardous areas. With NEMA 4/4x ratings. The robust engineering, industrial-grade construction, and UL Listing are the reasons that the Kooltronic Hazardous Location Series Air Conditioners provide the durability and safety required by hazardous location applications.
HL48LV Series has been granted a patent by the U.S. Patent & Trademark Office (U.S. Patent No. 9,157,670 B2). All electrical components are located in a sealed pressurized compartment, representing a major advance in safety and reliability. This design utilizes the electrical enclosure's existing purge system and allows for general-purpose components to be used, reducing both initial and service costs.
HL48LV Series offers capacities up to 9,000 BTU/H in single and 3-phase power. Many features such as a programmable thermostat, compressor short cycling protector, and Hi/Lo temperature alarm are standard. These units are offered at a lower cost easily maintained when compared to traditionally designed hazardous locations. These stainless steel units are used where hazardous gases may be present and are also suitable for corrosive.
| Model | KA6C9HL48LV | K2A6C9HL48LV |
| NEMA Rating | 4/4X | 4/4X |
| UL/CUL Listed or Recognized | Listed | Listed |
| BTU/H Capacity | 9000 | 9000 |
| 95/95 Rating BTU/H | 8000 | 8000 |
| Ambient Temp. | ||
| Max. ºF / Min. ºF | 125/-20 | 125/-20 |
| Min. ºC / Min. ºC | 52/-28 | 52/-28 |
| Volts | 115 | 230 |
| Hz | 60 | 50 |
| Running Amps | 18 | 9 |
| Approx. Weight | ||
| Lbs. | 122 | 122 |
| Kg. | 56 | 56 |
| Rating shown is for operation at maximum ambient temperature. | ||
| Pressurized Compartment Volume is 3.0 cu. ft., Air Leakage @ 0.25 i.w.g Pressure is 0.1 CFM |
No reviews yet — be the first to review this product.