Intrinsically Safe James Industry Exit Light J Series
The Intrinsically Safe James Industry Exit Light J Series system showcases exceptional features, including extended 3-hour emergency operation, customizable exit legends and multiple language options, adaptable installation with 3/4″ NPT or M25 conduit hubs, efficient low energy consumption lasting up to 50,000 hours, enhanced visibility through an edge-lit design, and durable IP66 Ingress Protection against dust and water ingress.
Operating in two distinctive modes, it either maintains the EXIT sign illuminated regardless of mains electricity status (Model 1) or activates the sign exclusively during power outages, remaining off when mains electricity is available (Model 2).
Its switch functionalities allow for single-press activation of the EXIT sign and indicator light flash sequence, prolonged press shutdown when disconnected, requiring mains electricity for reactivation, and automated monthly and annual inspections indicated by corresponding flash sequences.
This adaptable system ensures prolonged emergency lighting, tailored functionality, and automated inspections, ensuring heightened safety and reliability. Additionally certified for various hazardous area classifications and crafted with high-quality materials, including A356T6 aluminum housing with a baked-on gray epoxy finish, stainless steel hardware, mounting sling, tempered glass EXIT Sign Plate, and a one-piece silicone gasket for robustness and protection.
Features:
- 3-hour Emergency Operation: Ensures prolonged functionality during outages.
- Customization: Offers alternate exit legends and multiple language options.
- Versatile Installation: Equipped with 3/4″ NPT or M25 conduit hubs for various setups.
- Efficiency: Low energy consumption with an extended lifespan of up to 50,000 hours.
- Edge-Lit Design: Features an edge-lit sign for optimal visibility.
- IP66 Ingress Protection: Resistant to dust and water ingress for durability.
The system provides two operational options:
- Model 1: EXIT sign remains illuminated regardless of mains electricity status.
- Model 2: EXIT sign only activates during power outages, staying off when mains electricity is available.
Explanation of Indicator Light:
- If three or two indicator lights remain on during initial power on, it is necessary to reset them by detecting the switch: press the switch “ON” for 5 to 6 seconds ->OFF ->ON.
- RED:
1. Fast charging for 2 hours.
2. Charging indicator, displaying 20% -80% battery capacity. - GREEN:
1. Trickle charging.
2. Charging indicator, displaying 80% -100% battery capacity.
3. Green light on when disconnecting the battery.: - RED and GREEN:
1. Red and Green flashes alternately for 5 minutes, indicating that it is at
2. 80% battery capacity. - YELLOW:
1. Discharge below 20%.
2. If the yellow light is on in any state, the product is out of order.
Description of Switch:
- Press the switch “ON” once, the EXIT sign and indicator light will flash once, with an ON/OFF interval of 10 seconds.
- With mains electricity disconnected, long press and hold the switch for 3 to 5 seconds to turn off the product. If the EXIT sign needs to be turned on again, it will be activated through mains electricity.
- The product will automatically have monthly inspection. EXIT sign and indicator light will flash once every 30 or 31 days.
- The product will automatically have an annual inspection. EXIT sign and indicator light will flash twice every year.
Specifications:
Technical Data | ||||||
Universal Input Voltage | 100-277VAC or 100-347VAC, 50/60Hz | |||||
Rated Wattage | 1W, 2W, 3W, 4W, 5W | |||||
Emgergency Time | 3H | |||||
Warranty | 5-year limited warranty | |||||
Temperature Rating (Ambient) | 14°F to +140°F (-10°C to +60°C) | |||||