Intrinsically Safe XDT Digital Dew Point Transmitter
The Intrinsically Safe XDT Digital Dew Point Transmitter is a digital dewpoint transmitter that continuously monitor air dryer performance, compressed air quality, and dry gas moisture from ambient dewpoint levels to as low as -100°C (-148°F). They are designed as compact, simple, and reliable instruments.
Features
- Monitor and control air dryers
- Monitor plastic dryers
- Monitor welding gases
- Monitor laser gases
- Petrochemical feedstock gases
- Natural gas processing, transportation
and distribution - Clean rooms
- Transformer and switch gear insulation gases
- Glove boxes
- Cryogenic gases
- Heat treating furnaces
- Industrial specialty gases
Specifications
– Sensor type: High capacitance Al2 O3
– Input Resolution: 0.1°C dewpoint
– Indicators: LCD with backlight, 3.5 digits and custom legends for units and mode, audio alert
– Engineering units: Dewpoint in °F and °C, ppmv, g H2 O/m3 , lbs H2 O/mm scf
– Controls: 4 push buttons, all settings stored in EEPROM
– Output options: 4-20mA, 0-24mA or voltage outputs, linear to selected engineering units, programmable span and range, 0.1°C dewpoint resolution. RS-232 , baud rate 9600, resolution 0.1°C dewpoint
– Isolation: Sensor is isolated from the power supply, analog output and RS-232
– Alarm relays option: Two programmable alarm relays with programmable variable hysteresis, rated at 10A @240V. Failure indication programmable to trigger alarm relays
– Audible Alarm: >80dB @ 3ft. with silence feature
– Visual Alarm: XDT display backlight will stay on as long as alarm condition exists
– Test feature: Test button allows testing of both visual and audible indicators
– Power requirements: 100 – 240 VAC, 50 or 60 Hz, autoranging or by order 12VDC or 15-30VDC 0.5A
– Connections: Pluggable screw terminal block
– Enclosure: Polycarbonate, Nema 4/4x
– Dimensions: W-12cm x H-16cm x D-9cm (W-4.7” x H-6.3” x D-3.5”); DIN 43700 – 8cm (3”) deep
– Temperature range of electronics: -10° to 50°C (14° to 122°F)
– Optional Features: A) Medical Breathing Air Monitoring and Alarm Option, complies with the recommendations of NFPA 99, 1996 edition B) On-board battery backed real-time clock option, facilitating Scheduled Timer Activated Single Point Self Calibration/Verification procedure for sample systems equipped with an electrically actuated switchover valve.
– Warranty: One year for full workmanship and defective parts
– Class I, Division 1 Groups A, B, C, & D; Class II Groups E, F, & G;
– Class I Division 2 Groups A, B, C, & D; Class II Groups F & G; EEx d[ia] IIB+H2