Kooltronic HL60LV Explosion Proof Air Conditioner

SKU: K3A6C24HL60LV
(1 customer review)

The Kooltronic HL60LV Explosion Proof Air Conditioner is approved for use in Class 1 Division 1 and Class 1 Division 2 hazardous environments. With NEMA 4/4x protection. 24,000 BTU/HR rating and 480 VAC/3/60HZ operations. It is equipped with closed-loop cooling, a compressor short-cycling protector, a programmable thermostat, a programmable temperature alarm, a stainless steel shell, interior, and exterior purge connections, internal corrosion protection, and epoxy-coated evaporator and condenser coils that are shock and vibration resistant.

Hazardous Area Rating

,

$16,45125

Shipping Time: 1-2 weeks

Need faster options? Contact our Hazardous Areas Experts now for quick alternatives!

Trusted Clients

  • Logo PH66
  • Logo  Exxon
  • Logo Bp
  • Logo Conoco Phillipis
  • Logo Irwing
  • Logo Bayer
  • Logo Tesoro
  • Logo Northen TIer
  • Logo Udelhoven
  • Logo Aloha petroleum
  • Logo Rand
  • Logo Arrow Energy
  • Logo Schlumber
  • Logo Afton
  • Logo Holly frontier
Similar Category:

Safe Heating and Cooling Equipment The Kooltronic HL60LV may be used in Class I Division I and Class I Division II hazardous situations. With NEMA 4/4x certification. The Kooltronic Hazardous Location Series Air Conditioners are built to withstand the rigors of hazardous locations because of their industrial-grade construction and UL Listing.

The United States Patent and Trademark Office has issued a patent to HL60LV (U.S. Patent No. 9,157,670 B2). A significant step forward in terms of both safety and dependability has been achieved by enclosing all electrical components in a pressurized chamber. To cut down on expenses, this design takes advantage of the electrical enclosure’s existing purge system and makes general-purpose components available.

There is a single-phase and three-phase version of the HL60LV. Compressor short-cycle protection and a high/low-temperature alert are among the many features that come as standard. Compared to typical hazardous sites, these units are more affordable and easier to maintain. These corrosive- and hazardous-gas-resistant stainless steel components are ideal for a variety of industrial applications.

Features:

  • All models UL Listed per UL 484, Special Purpose Air Conditioners
  • All models UL Recognized per NFPA 496: 2013, Purged and Pressurized Enclosures for Electrical Equipment
  • Meets NEC Class I Division 1, Groups A, B, C & D Hazardous Locations when used with an approved Type X Purge System on the electrical enclosure.
  • Meets NEC Class I Division 2, Groups A, B, C & D Hazardous Locations when used with an approved Type Z Purge System on the electrical enclosure.
  • Temperature Classification is T-4, 275°F/135°C
  • Maintains NEMA Type 12, 3R & 4/4X Ratings per UL 50, Cabinets and Boxes
  • 480 Volt, 60 Hz, 24,000 BTU/H
  • 60″H x 24″W x 22″D Unit Dimension without pallet
  • 68″H x 30″W x 35″D Unit Dimension with pallet
  • 300 lbs Unit Weight with pallet
  • Closed-Loop Cooling
  • Compressor Short Cycle Protector
  • Filter
  • Interior and Exterior Purge Connections
  • Internal Corrosion Protection
  • Zero ODP Refrigerant
  • 1-year Factory Warranty
  • Made in the USA

Specifications:

ModelK3A6C24HL60LV
NEMA Rating4/4X
UL/CUL Listed or RecognizedListed
BTU/H Capacity24000
95/95 Rating BTU/H21600
Ambient Temp.
Max. ºF / Min. ºF125/-20
Min. ºC / Min. ºC52/-28
Volts480
Hz60
Running Amps10
Approx. Weight
Lbs.328
Kg.150
Rating shown is for operation at maximum ambient temperature.
Pressurized Compartment Volume is 18.0 cu. ft., Air Leakage @ 0.25 i.w.g Pressure is 0.4 CFM

Resources:

Reviews & Questions

Share your thoughts!

5 out of 5 stars

1 review

Let us know what you think...

One review with a 5-star rating

  1. archeal

    archeal

    Rated at 24,000 BTU/HR and operable at 480 VAC/3/60HZ. Certified Class I Division I and Class I Division II use in hazardous areas. Built and packaged to withstand the shock and vibration.

    Upvote if this was helpful (0) Downvote if this was not helpful (0) Flag for removal

    Something wrong with this post? Thanks for letting us know. If you can point us in the right direction...

×

Login

Continue as a Guest