E+E Elektronik HTS201 Room Sensor for Relative Humidity and Temperature
Hazardous location E+E Elektronik HTS201 Room Sensor for Relative Humidity and Temperature delivers precise and reliable measurements of relative humidity (RH) and temperature (T) in residential and commercial building automation. Its patented sensor technology ensures outstanding measurement performance, resilient even in dusty environments. The innovative enclosure prevents false air ingress and minimizes self-heating.
This device provides RH and T data through two analog outputs or via the digital RS485 interface supporting Modbus RTU or BACnet MS/TP protocols. Additionally, it offers dewpoint temperature (Td) data through Modbus RTU and BACnet MS/TP.
Featuring a functional design, the elegant enclosure adheres to regional standards and offers an optional display. Its construction simplifies installation, with a back cover housing push-in spring terminals separately from the electronics in the front cover. This allows easy commissioning by attaching the active part just before use and facilitates swift, tool-free replacement of the active component.
Configuration is streamlined for the digital version via PC, using the free PCS10 Product Configuration Software and an optional configuration adapter.
HTS201 is available in both US and EU formats, with or without a display, catering to different preferences and requirements.
Features:
Measurement Performance:
- High RH/T Accuracy: Ensures precision in measurements.
- Excellent Long-Term Stability: Consistent performance over time.
- State-of-the-Art E+E RH/T Sensing Element: Utilizes advanced technology for accuracy.
- Protected by E+E Proprietary Coating: Shields the sensor for extended lifespan.
- Patented Sensor Technology: Innovative technology for superior performance.
Enclosure and Connection:
- Innovative Design Avoids False Air Ingress: Prevents inaccurate readings.
- Time-Saving Installation and Wiring: Quick and efficient setup.
- Snap-On Without Tools: Easy assembly and maintenance.
- Push-In Spring Terminals: Simplifies connections.
- All Electronics Inside Front Cover: Ensures protection and convenience.
- Smooth Cover Surface: Repels dust and eases cleaning.
- Dust Repellent and Easy Cleaning: Maintains optimal functionality.
- EU and US Format: Available in regional standards.
- UL94HB Approved Enclosure Material: Ensures safety standards compliance.
Outputs:
- Two Analog Outputs: Provides 0-10V and 4-20mA options.
- RS485 Interface with Modbus RTU and BACnet MS/TP: Digital interface for data transmission.
- Large Graphic Display: Offers clear visual data representation.
Inspection Certificate:
- According to DIN EN 10204-3.1: Ensures compliance with inspection standards.
- Available via E+E Certificate Service: Accessible documentation for validation.
Protective Sensor Coating: The proprietary coating extends sensor lifespan, ensuring optimal performance in corrosive environments like offshore applications. It also enhances long-term stability in dusty, dirty, or oily conditions by preventing impedance caused by deposits on the sensor surface.
Specifications:
Technical Data | |||
Measurands | |||
Relative Humidity (RH) | |||
Measuring range | 0...100 %RH, non-condensing | ||
Accuracy1 incl. hysteresis, non-linearity and repeatability 0...100 %RH | ±(2 + 0.003 * mv) %RH | mv = measured value | |
Temperature dependency of electronics, typ | 0.008 % RH / °C (0.004 %RH / °F) | ||
Factory calibration uncertainty2) @ 23 °C (73 °F) | |||
0...90 %RH | ±(0.7 + 0.003 * mv) %RH | mv = measured value | |
>90...100 %RH | ±1 %RH | ||
1) Defined against E+E calibration reference at 23 °C (73 °F). With supply voltage 24 V DC, 0.2 m/s (39. 4 ft/min) medium flow and load resistor 250 Ω for version with current output. | |||
2) Defined at with an enhancement factor k=2, corresponding to a confidence level of 95 %. | |||
Temperature (T) | |||
Measuring range | -30...+60 °C (-22...+140 °F) | ||
Accuracy1 | |||
0- 10 V, RS485 | ±0,25 °C (±0.14 °F) | ||
4 - 20 mA (2-wire) | ±0,38 °C (±0.21 °F) | ||
Temperature dependency of electronics, typ. | 0.006 K/K | ||
Factory calibration uncertainty2) @ 23 °C (73 °F) | ±0.1 °C (±0.056 °F) | ||
1) Defined @ 23 °C (73 °F) against E+E calibration reference. With supply voltage 24 V DC, 0.2 m/s (39. 4 ft/min) medium flow and load resistor 250 Ω for version with current output. | |||
2) Defined with an enhancement factor k=2, corresponding to a confidence level of 95 %. | |||
Calculated Physical Quantity | |||
from | up to | unit | |
Dew point temperature Td | -30 (-22) | 60 (140) | °C (°F) |
Outputs | |||
Analogue | |||
T: acc. to ordering guide | 0 - 10 V | -1 mA < IL < 1 mA | IL = load current |
RH: 0...100 % | 4 - 20 mA (2-wire) | RL < (V+ - 10) / 0.02 < 500 Ω | RL = load resistance |
Digital | |||
Digital interface | RS485 (HTS201 = 1 unit load) | ||
Protocol | Modbus RTU | ||
Factory settings | Baud rate according to ordering guide, 8 data bits, parity even, 1 stop bit, Modbus address 45 | ||
Supported Baud rates | 9 600, 19 200 and 38 400 | ||
Measured data type | FLOAT32 and INT16 | ||
Protocol | BACnet MS/TP | ||
Factory settings | BACnet address 45 | ||
Supported Baud rates | 9 600, 19 200, 38 400, 57 600, 76 800 and 115 200 | ||
1) Ex works: see ordering guide | |||
General | |||
Power supply class III USA & Canada: Class 2 supply necessary, max. voltage 30 V DC | |||
0 - 10 V, RS485 | 15 - 35 V DC or 24 V AC ±20 % | ||
4 - 20 mA (2-wire) | 10 + 0.02 x RL < V+ < 35 V DC (RL < 500 Ω) | RL = load resistance | |
Current consumption, typ | @ 24 V DC | @ 24 V AC | |
0 - 10 V | 6 mA | 14 mArms | |
4 - 20 mA | Acc. to output current | Acc. to output current | |
RS485 | 5 mA | 12 mArms | |
Electrical connection | Push-in spring terminals max. 1.5 mm2 (AWG 16) | ||
Display | 1.8" LCD, dot-matrix, 2 lines, visible area 38 x 31 mm (1.5" x 1.2") | ||
Humidity range | |||
Operation | 0…100 %RH non-condensing | ||
Storage | 0…95 %RH non-condensing | ||
Temperature range, operation and storage | |||
without display | -30...+60 °C (-22...+140 °F) | ||
with display | -20...+60 °C (-4...+140 °F) | ||
Enclosure | |||
Material | PC (Polycarbonate), RAL 9003 (signal white), UL94 HB approved | ||
Protection rating | IP30 | ||
Electromagnetic compatibility | EN 61326-1 | EN 61326-2-3 | Industrial environment |
FCC Part15 Class B | ICES-003 Class B | ||
Shock and vibration | Tested according to EN 60068-2-64 and EN 60068-2-27 | ||
Conformity | CE & UKCA | ||
Configuration | PCS10 Product Configuration Software (free download) and optional configuration adapter |